Share:


QS061P-A2

  • Manufacturer : Mitsubishi Electric

  • QS061P-A2

  • Safety power supply unit QS 061 P - A 2

  • Base mounting position : QS series power supply unit mounting slot

  • Conformity base unit : QS034B

  • Input supply voltage : AC 200 - 240 V (-15% to + 10%)

  • Input frequency : 50/60 Hz ± 5%

  • Input voltage distortion ratio : Within 5%

  • Input maximum apparent power : 125 VA

  • Inrush current : 20 A within 8 ms

  • Rated output current DC 5V : 6 A

  • Overcurrent protection DC 5V : 6.6 A or more

  • Overvoltage protection DC 5V : 5.5 to 6.5 V

  • efficiency : over 70

  • Allowable momentary power failure time : Within 20 ms

  • Withstand voltage : Input . LG collective and output . FG all together AC 2830 Vrms / 3 cycles (altitude 2000 m)

  • Insulation resistance : Input . LG collective and output . Between FG batch, input batch and LG, batch output and FG: 500 MV DC insulation resistance meter 10 MΩ or more

  • Operation indication : LED indication (normal: green lighting, abnormal: lights off)

  • fuse : Built-in (user replaceable)

  • Contact output unit Use : ERR contact

  • Rated switching voltage / current : DC 24 V 0.5 A

  • Minimum opening / closing load : DC 5 V 1 mA

  • Response time OFF → ON : 10 ms or less

  • ON → OFF : 12 ms or less

  • lifespan mechanical : Over 20 million times

  • Electrical : Rated switching voltage / current load: 100 thousand times or more

  • Surge suppressor : None

  • fuse : None

  • External wiring connection method : Screw terminal block (M3.5 screw)

  • External dimensions Height (H) : 98 mm

  • Width (W) : 55.2 mm

  • Depth (D) : 115 mm



 Inquiry - QS061P-A2