Manufacturer : Mitsubishi Electric
-
QS061P-A2
-
Safety power supply unit QS 061 P - A 2
-
Base mounting position : QS series power supply unit mounting slot
-
Conformity base unit : QS034B
-
Input supply voltage : AC 200 - 240 V (-15% to + 10%)
-
Input frequency : 50/60 Hz ± 5%
-
Input voltage distortion ratio : Within 5%
-
Input maximum apparent power : 125 VA
-
Inrush current : 20 A within 8 ms
-
Rated output current DC 5V : 6 A
-
Overcurrent protection DC 5V : 6.6 A or more
-
Overvoltage protection DC 5V : 5.5 to 6.5 V
-
efficiency : over 70
-
Allowable momentary power failure time : Within 20 ms
-
Withstand voltage : Input . LG collective and output . FG all together AC 2830 Vrms / 3 cycles (altitude 2000 m)
-
Insulation resistance : Input . LG collective and output . Between FG batch, input batch and LG, batch output and FG: 500 MV DC insulation resistance meter 10 MΩ or more
-
Operation indication : LED indication (normal: green lighting, abnormal: lights off)
-
fuse : Built-in (user replaceable)
-
Contact output unit Use : ERR contact
-
Rated switching voltage / current : DC 24 V 0.5 A
-
Minimum opening / closing load : DC 5 V 1 mA
-
Response time OFF → ON : 10 ms or less
-
ON → OFF : 12 ms or less
-
lifespan mechanical : Over 20 million times
-
Electrical : Rated switching voltage / current load: 100 thousand times or more
-
Surge suppressor : None
-
fuse : None
-
External wiring connection method : Screw terminal block (M3.5 screw)
-
External dimensions Height (H) : 98 mm
-
Width (W) : 55.2 mm
-
Depth (D) : 115 mm
Inquiry - QS061P-A2