Share:


FX2NC-16EX

  • Manufacturer : Mitsubishi Electric

  • FX2NC-16EX

  • Input extension block

  • Application sequencer : FX1NC, FX3GC, FX2NC, FX3UC

  • mass : 0.15 Kg

  • Rated voltage : Internal power supply from the sequencer

  • power consumption : 2.2 W

  • Input specification :

  • Number of input points : 16 points

  • Input connection shape : connector

  • Input format : sink

  • Input signal voltage : DC 24 V + 20% - 15% ripple (pp) within 5%

  • Input impedance : 4.3 kO

  • Input signal current : 5 mA / 24 VDC

  • Input ON sensitivity current : 3.5 mA or more

  • Input OFF sensitivity current : 1.5 mA or less

  • Input response time : About 10 ms

  • Input signal format : No-voltage contact input or NPN open collector transistor

  • Input circuit insulation : Photocoupler insulation

  • Input operation display : LED ON when input is ON

  • Ambient temperature : 0 to 55 ° C. ... Operating -20 to 70 ° C. ... Save

  • Relative humidity : 35 to 85% RH (noncondensing).... in operation

  • Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2

  • Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 Ten times in each of X, Y, Z directions (80 minutes in total in total) The criterion is based on IEC 61131-2

  • Impact resistance : 147 m / s 2 , working time 11 ms, criterion for judgment three times in X, Y, Z directions by sine half-wave pulse is according to IEC 61131-2

  • Noise immunity : Noise voltage with 1,000 Vp-p, noise width 1 µs, rising 1 ns, with noise si

  • tor with period of 30 to 100 Hz



 Inquiry - FX2NC-16EX